Director: Kyra MooreThe primary concern regarding the disposal of used fluorescent lamp ballasts is the health risk associated with polychlorinated biphenyls (PCBs). Human exposure to these possible carcinogens can cause skin, liver and reproductive disorders. Fluorescent and high-intensity discharge lamp ballasts contain a small capacitor that may hold high concentrations of PCBs (greater than 90 percent pure PCBs or 900,000 parts per million). The chemical compounds were widely used as insulators in electrical equipment such as capacitors, transformers, switches and voltage regulators through the late 1970s. The Toxic Substances Control Act was enacted in 1976 and subsequently banned the production of PCBs in the United States. The proper method for disposing of used ballasts depends on several factors, such as the type and condition of the ballasts and the regulations and recommendations in effect. Toxic Substances Control Act specifies the disposal method for ballasts that are leaking PCBs. In addition, generators of PCB-containing ballast wastes may be subject to notification and liability provisions under the Comprehensive Environmental Response, Compensation, and Liability Act of 1980 (CERCLA) – also known as “Superfund”. (Note: PCBs are not regulated as hazardous waste; however, there may be other components in the ballast that would cause it to test out as a hazardous waste. Hazardous waste is not covered in this technical bulletin. Additional regulations will need to be met if the ballast contains hazardous waste.)
Light ballasts are the primary electric components of fluorescent light fixtures and are generally located within the fixture under a metal cover plate. The ballast units are generally composed of a transformer to reduce the incoming voltage, a small capacitor (that may contain PCBs) and possibly a thermal cut-off switch or safety fuse. These components are surrounded by a tarlike substance that is designed to muffle the noise that is inherent in the operation of the ballast. When a ballast unit fails, excessive heat can be generated which will melt or burn the tar material, creating a characteristic foul odor.
In considering causes of ballast failure, some privately conducted tests have indicated that operation of power saving lamps with standard ballast or standard lamps with power-saving ballast tends to significantly increase the ballast operating temperature and decrease its normal life span. It appears that ballasts will fail less frequently if standard lamps are used only with standard ballasts and power-saving lamps with power-saving ballasts. Fluorescent lamps should be changed in pairs: new lamps should not be used with old lamps.
When upgrading lighting, make sure your contractor removes all disconnected PCB-containing ballasts from the light fixtures. Non-leaking PCB-containing ballasts may still pose a hazard if left in upgraded fixtures, especially in the case of fire.
Use the following guidelines to identify ballasts that contain PCBs:
It is extremely important to find out if a ballast containing PCBs is leaking before you remove it from the fixture, so that you can handle it properly.
The Environmental Protection Agency recommends the following for anyone with a fluorescent light ballast leaking PCBs:
A puncture or other damage to a ballast in a lighting system exposes an oily tar-like substance. If this substance contains PCBs, the ballast and all materials it contacts are considered PCB waste and are subject to Toxic Substances Control Act requirements. Use trained personnel or contractors to handle and dispose of leaking PCB-containing ballasts.
Arrangements must be made with a facility for the pick-up, manifesting and shipment of ballasts, PCB-soiled items or fluorescent fixtures containing PCBs, to an approved chemical waste processing site. These firms will also perform minor PCB spill cleanups and arrange for the removal of PCB capacitors. (Review Missouri Commercial Hazardous Waste Facilities - PUB968) Leaking PCB-containing ballasts must be incinerated in an approved high-temperature incinerator.
Non-leaking small PCB capacitors (lighting ballasts) are not required to be incinerated. There are several options for disposal of non-leaking ballasts.
This disposal method is the one preferred by many companies because it destroys PCBs, removing them from the waste stream permanently removing the potential for future CERCLA liability. Incinerating PCB-containing ballasts costs more than sending them to a hazardous waste landfill or a sanitary landfill and but this additional cost is one many organizations are willing to absorb to limit future liability.
You may recycle used non-leaking ballasts despite PCBs. Recyclers remove the PCB-containing materials (i.e., the capacitor and possibly the asphalt potting material surrounding the capacitor) for incineration or land disposal. Metals, such as copper and steel, can be reclaimed from the ballasts for use in manufacturing other products. All PCB-containing ballasts must be shipped using a hazardous waste manifest and transported by a hazardous waste transporter registered by the EPA to transport PCBs.
PCB-containing ballasts may also be disposed in a chemical or hazardous waste landfill. Chemical or hazardous waste landfill disposal is less expensive than high-temperature incineration or recycling, but does not eliminate PCBs from the waste stream permanently. While chemical or hazardous waste landfill disposal is an acceptable, regulated disposal method, your organization may be legitimately concerned about potential CERCLA liability using this method.
Non-leaking PCB-containing ballasts may be disposed of in a sanitary landfill. While this type of disposal is allowed, there is a high potential of CERCLA liability using this method.
Note: CERCLA regulates the disposal of non-leaking PCB-containing ballasts. CERCLA requires building owners and generators to notify the National Response Center at 1-800-424-8802 when disposing of a pound or more of PCBs (roughly equivalent to 10-12 fluorescent ballasts) in a 24-hour period. As a generator of PCB-containing ballast wastes, you could be liable in any subsequent Superfund cleanup at a municipal, hazardous, or chemical disposal site, incinerator, or recycling facility. Your contractor should provide you with documents verifying the disposal method.
Despite the disposal method selected, ballasts are packed, according to PCB regulations, in 55-gallon drums for transportation.
Transporters of leaking PCB ballasts and PCB contaminated waste need to be licensed hazardous waste transporters. All PCB-containing ballasts must be shipped using a hazardous waste manifest and transported by a hazardous waste transporter registered by the EPA to transport PCBs.
To track transported Toxic Substances Control Act or hazardous waste (leaking PCB ballasts and PCB-contaminated waste), generators must prepare a hazardous waste manifest. The manifest identifies the type and quantity of waste, the generator, the transporter and its ultimate destination. Please contact the Missouri Department of Natural Resources’ Hazardous Waste Program for blank copies of manifests.
The manifest must accompany the waste wherever it travels. Each handler of the waste must sign the manifest and keep one copy. When the waste reaches its destination, the owner of that facility returns a copy of the manifest to the generator to confirm that the waste arrived. If the waste does not arrive as scheduled, generators must immediately notify the Missouri Department of Natural Resources’ Hazardous Waste Program, so that they can investigate and act appropriately. Copies of the completed manifests should be kept for at least three years.
Copies of the Revised Statutes of Missouri are available through the Reviser of Statutes at 573-526-1288 and are available online at www.moga.state.mo.us. Copies of the Missouri Code of State Regulations are available through the Missouri Secretary of State at 573-751-4015 and are available online at http://www.sos.mo.gov/adrules/csr/current/10csr/10csr. Federal regulations may be viewed at federal depository libraries or may be purchased from a U.S. Government Bookstore, the U.S. Government Printing Office, or from a commercial information service such as the Bureau of National Affairs. Federal Regulations are also available online at http://www.ecfr.gov/cgi-bin/ECFR?page=browse.
Nothing in this document may be used to implement any enforcement action or levy any penalty unless promulgated by rule under chapter 536 or authorized by statute.